Call toll free: 1-866-311-1945 | sales@excessups.ca
Your Region:

Liebert GXT2 6000VA 4200W RM 4U 208V/120V Split Phase GXT2-6000RT208 - Refurbished

Liebert GXT2 6000VA 4200W RM 4U 120V/208V UPS
Model: GXT2-6000RT208
Maximum Output: 6000VA / 4200W 120/208V
Input: L14-30P - Split Phase
Double Conversion Online UPS - Pure Sinewave Output
Refurbished with New Batteries
CAD $2,419.99
Availability: In stock

Description

Details

Manufacturer: Liebert
Model: GXT2-6000RT208 Liebert Online Double Conversion Rackmount 4U UPS - 120V / 208V - Split phase
Condition: Refurbished with New Batteries
Part Number: GXT2-6000RT208
Warranty: 1 Year Full Replacement Warranty, additional warranty available

The GXT2-6000RT208 comes refurbished with new batteries. The Liebert UPS comes with a one year replacement warranty. Additional warranty of up to 3 years is available for your convenience.

  • True On Line (Double Conversion) Technology
  • User replaceable batteries without removing GXT2 from rack
  • Wide input voltage window allows UPS support without going to battery, extending systems availability
  • Built in Surge Suppression
  • SNMPE3 compatible
  • External plug and play, 2U battery cabinets available
  • Configurable as rack or tower Specifications

GXT2-6000RT208 Specifications:

Output

  • Capacity 6000VA (4200 Watts)
  • Nominal Voltage 120/208 VAC
  • L1-L2 Factory default output phase angle: 120 Degrees
  • Allowable output phase angle: 120, 180 or 240 Degrees, auto-sending on initial application of AC
  • Factory default L1-N, L2-N VAC: 120 VAC
  • User configurable L1-N, L2-N VAC: 100, 110, 115, 120, 127 VAC +/- 3%
  • Output connections: Frequency 50/60 Hz
    • (1) L6-30R
    • (1) L6-30R
    • (4) 5-20R (Standard 120V 3-prong receptacles will also accept 20Amp straight plug also known as “T” plug)
  • Waveform Sinewave

Input

  • Input Voltage 120/208 VAC at 120 degrees
  • Frequency 50/60 Hz
  • L1-L2 Input Phase Angle 120 Degrees
  • Allowable Input Phase Angle 120, 180, 240 degrees. Auto sensing on application of AC.
  • Factory default L1-N, L2-N VAC: 120 VAC Nominal
  • User configurable L1-N, L2-N VAC: 100, 110, 115, 120, 127 VAC
  • Input power connection: L14-30P

Batteries

  • Type Valve-regulated non-spillable, flame-retardant, sealed lead-acid batteries
  • Runtime at full load (4200 Watts) 5 minutes
  • Runtime at 75% load (3150 Watts) 8 minutes
  • Runtime at 50% load (2100 Watts) 14 minutes
  • Runtime at 25% load (1050 Watts) 32 minutes
  • Runtime at minimal load (420 Watts) 75 minutes
  • Replacement battery kit URBC120912
  • Recharge Time 6 hours to 90% capacity
  • External Battery Cabinet for extended runtime capability GXT2-144VBATT

Physical

  • Width 16.9 inches (430 mm)
  • Depth 24.2 inches (615 mm)
  • Height 6.9 inches (4U) (176 mm)
  • Weight 146 lbs. (66.1 Kg)
  • Audible Noise <50 dBA at 1 meter from front or sides

Copmpliance

  • UL 1778
  • c-UL Listed
  • FCC Part 15 Subpart B Class A
  • IEEE/ANSI C62.41 Category A & B
  • ISTA Procedure 1A

Additional Info

Additional Info

Manufacturer Liebert
Form Factor Rackmount
Waveform in Battery Mode Pure Sinewave
Input Voltage 120V AC, 208V AC
Output (VA) 6000VA
Output Voltage No
PDU Total Outlets No

You may also be interested in