Vertiv Liebert GXT5 UPS 8000VA 8000W RM 5U 208V/240V GXT5-8000HVRT5UXLN - Refurbished

Vertiv Liebert GXT5 8kVA 8kW RM/Tower 5U 208V/240V
Model: GXT5-8000HVRT5UXLN
Input: Hardwire 208V/240V - L1-L2-G
Output:
(2) L6-20R, (2) L6-30R. Hardwire In/Out
Online, Double-Conversion UPS - Sine wave Output
New batteries, refurbished UPS
1 Year Warranty Included

In stock

Manufacturer: Vertiv
Model: Vertiv Liebert GXT5 8000VA 8000W RM/Tower 5U 208V/240V - Online Double Conversion UPS

Condition: New batteries, refurbished UPS
Part Number: GXT5-8000HVRT5UXLN
Maximum output:
 8000W / 8000VA
Typical backup time
at half load: 9.5 minutes (4000 Watts)
Typical backup time
at full load: 3.5 minutes (8000 Watts)
Warranty:
1 year full replacement warranty
Included: UPS, rack ears, rail kit, tower stand (feet), USB cable


Vertiv Liebert GXT5 8000VA 8000W 208V/240V GXT5-8000HVRT5UXLN User's Manual

 


GXT5-8000HVRT5UXLN - Vertiv UPS 8000VA / 8000W Specifications:


Overview:

Power Rating

8,000VA / 8,000W

Input Voltage

Typical: 208VAC / Range: 176-288VAC - L1-L2-G

Output Voltage

200/208/220/230/240 VAC (user-configurable)

Efficiency

Up to 98% Active ECO Mode; up to 95% on-line mode

Wiring

Hardwired in/out + Output: 2 x L6-20R, 2 x L6-30R


Operational Conditions:

Operating Temperature

+32 to +104 °F (0 to 40 °C)


Physical:

Dimensions (inch/mm)

16.9 × 24.8 × 8.5 (430×630×217)

Weight (lbs/kg)

75.5 (166.4)


Input AC:

Operating Frequency, Nominal

50 or 60 Hz (factory-default is 60 Hz)

Factory-default VAC

208 VAC - L1-L2-G

User-configurable VAC

200/208/220/230/240 VAC
(Adjustable using operation/display configuration options)

Operating voltage range without battery operation

176 – 288 VAC (100 – 176VAC with power derating)

Maximum Allowable VAC

288 VAC

Input Frequency without Battery Operation

40 – 70 Hz

Input Power Connection

PD5-CE10HDWRMBSU


Output AC:

Output Receptacles

(2) NEMA L6-20R

(2) NEMA L6-30R

Hardwired in/out

 

AC-AC Efficiency

95%

Factory-default VAC Frequency

208 VAC, 60 Hz

Output Voltage

208 VAC Nominal
Adjustable to 200/220/230/240 VAC

Output Power Connection

PD5-CE10HDWRMBSU

Waveform (on battery)

Sine wave

Utility (AC) Mode Overload

>150% minimum 200 mS,
125 – 150% for 60 seconds;
105 – 125% for for 5 minutes;
≤ 105% continuous


Interfaces / Ports:

Interface Options

Optional Vertiv™ IS-UNITY-DP SNMP/Webcard, USB, RS485, RS232, terminal block, external battery connector

Protocols

SNMP and web management enabled with an optional Vertiv IS-UNITY-DP communications card; serial connection for out-of-band management

Control Panel

Full-color graphic LCD with gravity sensing orientation, provides insight to UPS status for easy installation, configuration and operation


Internal Battery Charger:

Charger Current, A

2.25A default, maximum 8A


Battery Parameters:

Type

Valve-regulated, non-spillable, lead acid

Quantity x Voltage x Rating

16 x 12V x 9.0AH

Backup Time (100% Load)

3.5 Minutes

Backup Time (50% Load)

9.5 Minutes

+1 External Battery Cabinet (100% Load)

9.5 Minutes

+1 External Battery Cabinet
(50% Load)

26 Minutes

Upper-limit selections

+10%, +15%, +20%; default +10%.

Lower-limit selections

-10%, -15%, -20%; default -15%

Disable-bypass operation

When the input frequency prevents synchronous operation


Environmental:

Operating Temperature, °F (°C)

+32 to +104 (0 to 40)
(no derating)

Storage Temperature, °F (°C )

5 to 104 (–15 to 40)

Relative Humidity

0% to 95%, non-condensing

Operating Elevation

Up to 3,000 m (9,842.5 ft) at 25°C (77°F) without derating

Audible Noise

<55 dBA,at 1 meter from the front,
<50 dBA, at 1 meter from rear
or sides


Agency:

Safety

IEC62040-1:2008 version, 
GS mark;
UL1778, c-UL listed

EMI/EMC/C-Tick EMC

IEC/EN/AS 62040-2 2nd
Ed (Cat 2 – Table 6); FCC Part 15 (Class A)
CISPR22 Class A (RFI)

ESD

IEC/EN EN61000-4-2, 
Level 4, Criteria A

Radiated Susceptibility

IEC/EN EN61000-4-3, 
Level 3, Criteria A

Electrical Fast Transient

IEC/EN EN61000-4-4, 
Level 4, Criteria A

Surge Immunity

IEC/EN EN61000-4-5,
Level 4, Criteria A;
ANSI C62.41 Category B

Transportation

ISTA Procedure 1E

Emissions

FCC Part 15 (Class A)


Miscellaneous:

Listings

ENERGY STAR® 2.0 certified, UL1778, c-UL listed, RoHS2, REACH

Topology

On-line double conversion UPS; flexible rack/tower form factor

 


The Vertiv™ Liebert® GXT5-8000HVRT5UXLN UPS delivers powerful, high-capacity power protection, ideal for critical infrastructure and edge applications. With an 8,000 VA / 8,000 W rating, this UPS leverages online double-conversion technology to provide continuous, clean power, ensuring critical systems remain protected from power disturbances. It operates efficiently across a wide voltage input range of 176–288 VAC, allowing for consistent performance even with fluctuations, while achieving up to 98% efficiency in ECO mode. The unit's unity power factor design further enhances power support, optimizing capacity and minimizing space requirements.


This UPS is designed for easy integration and comprehensive remote management, featuring an intuitive LCD interface for on-site monitoring, configuration, and diagnostics. Remote management is enabled via an optional Vertiv RDU101 communications card, which is compatible with Vertiv™ Power Insight software, environmental sensors, and Vertiv™ LIFE™ Services. The GXT5-8000HVRT5UXLN also supports scalable runtime with external battery cabinets, which adjust automatically to report available power, offering flexibility for extended backup needs. With its built-in maintenance bypass and advanced overload protection, this UPS ensures resilient, uninterrupted power for mission-critical applications.



To start the UPS:

  • Check the Maintenance Bypass: Ensure the maintenance bypass switch is in the open (off) position, and verify that the guard is securely in place.

  • Verify Emergency Power Off (EPO) Connection: Confirm that the REPO connector at the rear of the unit has a jumper between pins 7 and 8, or ensure it is correctly wired to a normally closed Emergency Power Off circuit.

  • Power Source Preparation: Ensure the breaker supplying power to the UPS is closed. If needed, press the input circuit breaker reset buttons located on the rear of the UPS.

  • Set Output Breakers: Close all output breakers on the rear of the UPS or in an external panel board if one is used.

  • External Battery Cabinets (if attached): If external battery cabinets are connected, close the breakers on the rear of each cabinet.

  • Power On the UPS: Press and hold the Power button on the operation and display panel until a confirmation dialog appears. Use the Up/Down arrows to select YES, then press Enter.

  • First-Time Startup Configuration: For initial setup, the Start-up Guidance wizard will launch. Follow the on-screen prompts to set up the basic operating parameters of the UPS.

 

To shut down the UPS:


Shutdown Instructions for the Vertiv™ Liebert® GXT5-8000HVRT5UXLN UPS:

  1. Initiate Shutdown: Press and hold the Power button for 2 seconds.

  2. Select Shutdown Mode: If the UPS is functioning normally without any faults, a menu will appear with two options:

    • Turn to Bypass – to transfer power to bypass mode.
    • Turn Off UPS – to power down the unit completely.
  3. Confirm Choice: Use the arrow buttons to select either Turn to Bypass or Turn Off UPS and press Enter. Then, select Yes to confirm or No to cancel, and press Enter to finalize your selection.