Model:
Refurbished Tripp Lite SmartPro UPS 3000VA 120V with New Batteries
Condition: Refurbished with New Batteries
Part Number: SMART3000CRMXL
Maximum output: 2880W / 3000VA
Typical backup time
at half load: 19.0 minutes (1220 Watts)
Typical backup time
at full load: 7.5 minutes (2880 Watts)
Warranty:
1 year full replacement warranty


Tripp Lite SmartPro UPS 3000VA SMART3000CRMXL Manual


SMART3000CRMXL - Tripp Lite SmartPro UPS 3000VA Specifications:

OUTPUT

Output Volt Amp Capacity (VA)

3000

Output Watt Capacity (watts)

2880

Output Capacity Details

Supports 3600 watts max with hardwire input

Nominal Output Voltage(s) Supported

120V

Frequency compatibility

60 Hz

Output voltage regulation (line mode)

-18%, +8%

Built-in UPS output receptacles

8 5-15/20R outlet(s); 1 L5-30R outlet(s)

Built-in controllable switched load banks

Three switchable single-outlet 5-15/20R load banks

Output circuit breaker

20A (x2) - each 20A breaker protects 4 5-15/20R outlets / 30A breaker protects L5-30R

Output AC waveform (battery mode)

Pure Sine wave


INPUT

Rated input current (at maximum load)

24A (L5-30P input), 30A (hardwire)

Nominal Input Voltage(s) Supported

120V AC

UPS input connection type

L5-30P; Hardwire

UPS Input cord length (ft.)

10 ft.

UPS Input cord length (m)

3.05

Recommended Electrical Service

120V 30A

Voltage compatibility (VAC)

120

Phase

Single-Phase


BATTERY

Full load runtime (minutes)

7.5 min. (2880w)

Half load runtime (minutes)

19 min. (1440w)

External battery pack compatibility

BP48V24-2U (limit 1); BP48V48RT4U (multi-pack compatible); BP48V27-2US (multi-pack compatible)

DC system voltage (VDC)

48

Battery recharge rate (included batteries)

Less than 7.2 hours from 10% to 90%

Replacement battery cartridge (internal UPS battery replacement)

RBC94-2U (quantity 2)

Battery Access

Battery access door allows hot swap battery replacement without powering connected equipment off


VOLTAGE REGULATION

Voltage regulation description

Automatic Voltage Regulation (AVR) circuits maintain clean, regulated computer-grade 120V nominal output, without using battery power, during brownouts to 83V and overvoltages to 145V

Overvoltage correction

Input voltages between 127 and 145V AC are reduced by 12%

Undervoltage correction

Input voltages between 96 and 108 are boosted by 12%

Severe undervoltage correction

Input voltages between 83 and 95 are boosted by 24%


LEDS ALARMS & SWITCHES

LED Indicators

5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status

Alarms

3 function audible alarm indicates power failure conditions (4 short beeps every 10 seconds), overload (continuous short beeps) and low battery (continuous tone)

Switches

Yes, includes 2 front panel mounted push-button switches for system enable, self-test and alarm cancel functions. Back panel includes battery charge level switch for internal or external battery configurations


SURGE / NOISE SUPPRESSION

UPS AC suppression joule rating

570 joules

EMI / RFI AC noise suppression

Yes

AC suppression response time

Instantaneous


PHYSICAL

Installation form factors supported with included accessories

2 post 19 inch rackmount

Installation form factors supported with optional accessories

4 post rackmount (4POSTRAILKIT); Tower (2-9USTAND)

Primary form factor

Rackmount

UPS / Power Module dimensions in primary form factor (height x width x depth / inches)

7 x 17.3 x 16.8

UPS / Power Module dimensions in primary form factor (height x width x depth / cm)

17.8 x 43.9 x 42.7

Rack Height

4U

UPS / Power Module weight (lbs)

102

UPS / Power Module weight (kg)

46.3

UPS Shipping dimensions (height x width x depth / inches)

13.2 x 23.6 x 22.8

UPS Shipping dimensions (height x width x depth / cm)

33.5 x 59.9 x 57.9

Shipping weight (lbs)

124

Shipping weight (kg)

56.3

Cooling method

Fan

UPS housing material

Steel


ENVIRONMENTAL

Operating Temperature Range

+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius

Storage Temperature Range

+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius

Relative Humidity

0-95%, non-condensing

AC mode BTU / hr. (full load)

408

Battery mode BTU / hr. (full load)

2149.5


COMMUNICATIONS

Communications interface

USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface

WatchDog compatibility

Yes, compatible with Tripp Lite's Watchdog system service to restore operation to locked equipment through soft reboot of application / OS or hard power off/on reboot of connected equipment ideal for unattended kiosk applications

EPO port

Includes RJ11 EPO (emergency power off) port and interconnection cable

SNMP compatibility

Yes, includes slot for optional SNMPWEBCARD accessory (#SNMPWEBCARD)

Software and cabling included

Yes, includes PowerAlert software CD-ROM and complete cabling


LINE / BATTERY TRANSFER

Transfer time

5 ms. (typical)

Low voltage transfer to battery power (setpoint)

83

High voltage transfer to battery power (setpoint)

145


SPECIAL FEATURES

Cold Start (startup in battery mode during a power failure)

Cold-start operation supported

High availability UPS features

Hot swappable internal UPS power module; hot-swap batteries

Appearance

Attractive black rackmount housing, optional use 2U black front bezel included to enable black color appearance


CERTIFICATIONS

Certifications

Tested to UL1778 (USA), CSA (Canada), NOM (Mexico), Class A (Emissions)

 