Description
Details
Manufacturer: Tripp Lite
Model: Tripp Lite SmartOnline UPS 1500VA 1200W, LCD, RM, 2U, 120V
Condition: New batteries, refurbished UPS
Part Number: SU1500RTXL2UA
Maximum output: 1200W / 1500VA
Typical backup time at half load:14 minutes (600 Watts)
Typical backup time at full load: 5 minutes (1200 Watts)
Warranty: 1 year full replacement warranty
Tripp Lite SmartOnline 1500VA 1200W RM 120V SU1500RTXL2UA User's Manual
SU1500RTXL2UA - Tripp Lite SmartOnline 1500VA Specifications:
Input:
Rated input current (Maximum Load) |
12A |
||
Nominal Input Voltage(s) Supported |
120V AC |
||
UPS Input Connection Type |
|
||
Input Circuit Breakers |
20A |
||
UPS Input Cord Length (ft.) |
10 |
||
UPS Input Cord Length (m) |
3.1 |
||
Recommended Electrical Service |
15A 120V |
||
Input Phase |
Single-Phase |
||
Input Frequency |
50/60Hz +/-5% |
Output:
Output Volt Amp Capacity (VA) |
1500 |
||
Output Capacity (kVA) |
1.5 |
||
Output Watt Capacity (Watts) |
1200 |
||
Output kW Capacity (kW) |
1.2 |
||
Output Capacity Details |
OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% load for 3 minutes; 150% load for 30 seconds and >150% load for 0.5 seconds before switching to BYPASS (when bypass input voltage and frequency are WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE bypass limits) |
||
Power Factor |
0.8 |
||
Crest Factor |
3:1 |
||
Frequency Compatibility |
50 / 60 Hz |
||
Frequency Compatibility Details |
Output frequency matches input nominal on startup, defaults to 60 Hz on cold-start |
||
Output Voltage Regulation (Line Mode) |
+/- 2% |
||
Output Voltage Regulation (Economy Line Mode) |
+/- 10% |
||
Output Voltage Regulation (Battery Mode) |
+/- 2% |
||
Load Management Receptacles |
Two switchable 5-15R load banks (bank 1 - two outlets, bank 2 - four outlets) |
||
Output AC Waveform (AC Mode) |
Sine wave |
||
Output AC Waveform (Battery Mode) |
Pure Sine wave |
||
Nominal Output Voltage(s) Supported |
120V |
||
Output Receptacles |
|
||
Individually Controllable Load Banks |
Yes |
Battery:
Battery Type |
Valve Regulated Lead Acid (VRLA) |
Full Load Runtime (min.) |
5 min. (1200w) |
Half Load Runtime (min.) |
14 min. (600w) |
Expandable Battery Runtime |
Extended runtime supported via optional external battery packs |
Expandable Runtime |
Yes |
External Battery Pack Compatibility |
BP48V24-2U (limit 1); BP48V60RT-3U (multi-pack compatible); BP48V27- 2US (multi-pack compatible) |
DC System Voltage (VDC) |
48 |
Battery Recharge Rate (Included Batteries) |
Less than 6 hours from 10% to 80% (typical, full load discharge) |
Battery Access |
Front panel battery access door |
Internal UPS Replacement Battery Cartridge |
RBC94-2U |
Battery Replacement Description |
Hot-swappable, user replaceable batteries |
Voltage Regulation:
Voltage Regulation Description |
Online, double-conversion power conditioning |
Overvoltage Correction |
Power-fail alarm can be silenced using alarm-cancel switch |
Undervoltage Correction |
Voltage boost of 12% applies when input voltage is between 96 and 108 |
Severe Undervoltage Correction |
Voltage boost of 24% applies when input voltage is between 83 and 95 |
User Interface, Alerts & Controls:
Switches |
2 switches control off/on power status and alarm-cancel/self-test operation |
Alarm Cancel Operation |
Power-fail alarm can be silenced using alarm-cancel switch |
Audible Alarm |
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions |
LED Indicators |
14 LEDs indicate line power, online mode, economy/bypass mode, on-battery, overload, battery low, replace battery and fault status information; 4-LED meter displays load and battery charge levels; LED panel rotates for viewing in rack/tower formats |
Surge / Noise Suppression:
UPS AC Suppression Joule Rating |
600 |
UPS AC Suppression Response Time |
Instantaneous |
UPS Dataline Suppression |
1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet |
EMI / RFI AC Noise Suppression |
Yes |
Physical:
Primary Form Factor |
Rackmount
|
Cooling Method |
Fan
|
Included Mounting Accessory Description |
Included 4POSTRAILKIT mounting bracket enables installation in 4 post racks from 20.5 to 36 inches (521 to 914mm)
|
Installation Form Factors Supported: |
4 post 19 inch rackmount & 2 post rack
|
Installation Form Factors Optional Accessories |
2 post rackmount ( 2POSTRMKITWM ); 2-4 post front rail rackmount ( UPSHDEARKIT ); 4 post rackmount short-depth ( 4POSTRAILKITWM ); Tower ( 2- 9USTAND ); Wallmount ( 2POSTRMKITWM )
|
Minimum Required Rack Depth with External Battery Pack (cm) |
66
|
Minimum Required Rack Depth with External Battery Pack (in.) |
26
|
Minimum Required Rack Depth without External Battery Pack (cm) |
56
|
Minimum Required Rack Depth without External Battery Pack (in.) |
22
|
Optional Mounting Accessory Notes |
Optional 2-9USTAND enables upright tower UPS placement; 2POSTRMKITWM enables wall-mount and 2-post rackmount installation; 4POSTRAILKITWM enables installation in 4-post short-depth racks from 14.5 to 23.5 inches (368 to 597mm); UPSHDEARKIT enables installation in 2 or 4-post racks using front vertical rails only, without rear support |
Primary UPS Depth (mm) |
483 |
Primary UPS Height (mm) |
89 |
Primary UPS Width (mm) |
445 |
Rack Height |
2U |
Shipping Dimensions (hwd / cm) |
23.37 x 59.44 x 49.53 |
Shipping Dimensions (hwd / in.) |
9.20 x 23.40 x 19.50 |
Shipping Weight (kg) |
27.94 |
Shipping Weight (lbs.) |
61.60 |
UPS Housing Material |
Steel |
UPS Power Module Dimensions (hwd, cm) |
8.89 x 44.45 x 48.26 |
UPS Power Module Dimensions (hwd, in.) |
3.5 x 17.5 x 19 |
UPS Power Module Weight (kg) |
20.00 |
UPS Power Module Weight (lbs.) |
44.1 |
Environmental:
Operating Temperature Range |
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
|
Storage Temperature Range |
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
Relative Humidity |
0 to 95%, non-condensing |
AC Mode BTU / Hr. (Full Load) |
612 |
AC Economy Mode BTU / Hr. (Full Load) |
216 |
Battery Mode BTU / Hr. (Full Load) |
667 |
AC Economy Mode Efficiency Rating (100% Load) |
95% |
Communications:
Network Management Cards |
SNMPWEBCARD ; TLNETCARD ; WEBCARDLX ; MODBUSCARD ; RELAYIOCARD - Not included |
Network Monitoring Port Description |
Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure communications; Economy-mode setting option is available using PowerAlert software and DB9 Serial cable connection OR via select Network Management Card options |
PowerAlert Software |
For local monitoring via the UPS’s built-in communication ports , download PowerAlert Local software at https://www.tripplite.com/poweralert |
Communications Cable |
USB and DB9 cabling included |
WatchDog Compatibility |
Supports Watchdog application, OS and hard-reboot restart options for remote applications |
Network Management Card Description |
Network management card optional |
Communications Interface |
Contact closure; DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface; USB (HID enabled) |
Additional Info
Additional Info
Manufacturer | Tripp Lite |
---|---|
Form Factor | Rackmount |
Waveform in Battery Mode | Pure Sinewave |
Input Voltage | 120V AC |
Output (VA) | 1500VA |
Output Voltage | 120V AC |
PDU Total Outlets | No |