Vertiv Liebert GXT5 1500VA 1350W RM 2U 120V
Model: GXT5-1500LVRT2UXL
Input: NEMA 5-15P (120V - 15A)
Output: (6) NEMA 5-15R
Double-Conversion Online UPS - Sine wave Output
New batteries, refurbished UPS
1 Year Warranty Included
In stock
Manufacturer: Vertiv, Liebert
Model: Vertiv Liebert GXT5 UPS 1500VA 1350W RM 2U 120V - Online double conversion UPS
Condition: New batteries, refurbished UPS
Part Number: GXT5-1500LVRT2UXL
Maximum output: 1350W / 1500VA
Typical backup timeat half load: 18.8 minutes (675 Watts)
Typical backup time at full load: 6.7 minutes (1350 Watts)
Warranty: 1 year full replacement warranty
Description: Vertiv Liebert GXT5-1500LVRT2UXL is a 1500VA / 1350W online double-conversion UPS designed for critical IT and network applications, delivering clean and consistent sine wave power with zero transfer time, featuring a wide input voltage range (60–150V) and user-selectable output voltage (110/115/120V), equipped with (6) NEMA 5-15R outlets, and a compact 2U rack/tower convertible design, includes internal valve-regulated lead-acid batteries providing up to 18.8 minutes of runtime at half load and 6.7 minutes at full load, with support for external battery cabinets to significantly extend runtime, built for high reliability with overload protection, low noise operation (<46 dBA), and compliance with UL, CSA, and FCC standards, refurbished with new batteries and backed by a 1-year full replacement warranty.
Liebert GXT5 1500VA 1350W GXT5-1500LVRT2UXL User's Manual
GXT5-1500LVRT2UXL - Liebert UPS 1500VA / 1350W Specifications:
Input:
|
Range |
Typical 120V |
|
Frequency |
40-70Hz; Auto Sensing |
|
Input Power Cord |
10 ft. attached w/ |
Output:
|
Output Receptacles |
|
||
|
Typical 120V |
110/115/120VAC |
||
|
Waveform |
Sine wave |
||
|
Utility (AC) Mode Overload |
>200% for 250ms; |
Battery:
|
Type |
Valve-regulated, non-spillable, lead acid |
|
Backup Time (100% Load) |
6.7 |
|
Backup Time (50% Load) |
18.8 |
|
+1 External Battery Cabinet |
32.4 |
|
+1 External Battery Cabinet |
79.7 |
Environmental Requirements:
|
Operating Temperature, °F (°C) |
+32 to +104 (0 to 40) |
|
Storage Temperature, °F (°C ) |
-4 to +140 (-20 to 60) |
|
Relative Humidity |
0% to 95%, non-condensing |
|
Operating Elevation |
10,000 ft. (3,000m) |
|
Storage Elevation |
50,000 ft. (15,000m) |
|
Audible Noise |
< 46dBA at 3 ft. (1m) front and side |
Physical:
|
Dimensions (inch/mm) |
16.9 x 18.5 x 3.4 (430 x 470 x 85) |
|
Weight (lbs/kg) |
46.2 (21) |
Communications & Management :
|
Control Interface |
LCD graphical display with keypad + Web interface (with optional network card) |
|
Front Panel |
Color LCD for real-time status, alarms, load %, battery level, and configuration settings |
|
Remote Monitoring |
Supported via optional communication cards (IS-Unity-DP IntelliSlot or Liebert® IntelliSlot™ RDU101 cards) |
|
Communication Slots |
1 × IntelliSlot port for optional network/relay cards |
|
Communication Ports |
USB, RS-232 (serial), dry contact (optional via card) |
|
Network Interface |
Optional (via Vertiv IS-UNITY-DP or equivalent) |
|
Protocols |
SNMP v1/v2c/v3, HTTP/HTTPS, SSH, Telnet, Modbus TCP/IP (with Unity card) |
|
Software Compatibility |
Vertiv Power Insight, Vertiv LIFE Services |
|
Remote Shutdown |
Supported (graceful shutdown via software/agents) |
|
Alarm System |
Audible alarms + visual indicators (LCD + LEDs) |
|
Alarm Types |
Power failure, low battery, overload, overtemperature, fault conditions |
|
Notifications |
Email alerts, SNMP traps, remote notifications (with network card) |
|
Event Logging |
Event history and fault logs via LCD and remote interface |
|
Data Logging |
Power events, runtime data, input/output conditions |
|
Firmware Upgrade |
Supported via USB or network interface (with card) |
|
User Access Control |
Role-based access (with network card interface) |
|
Security |
HTTPS, SSH, SNMPv3 encryption/authentication (with Unity card) |
|
Emergency Power Off (EPO) |
Supported (rear panel EPO port) |
|
Generator Compatibility |
Yes (wide input tolerance and frequency range) |
Agency:
|
Surge Immunity |
ANSI C62.41 Category B |
|
Transportation |
ISTA Procedure 1A |
|
Safety |
UL 1778 4th Edition and CSA |
|
Emissions |
FCC Part 15 (Class A) - |
|
Environmental |
WEEE and ROHS2 REACH |