Liebert

Vertiv Liebert GXT5 1500VA 1350W RM 2U 120V GXT5-1500LVRT2UXL - Refurbished

Vertiv Liebert GXT5 1500VA 1350W RM 2U 120V
Model: GXT5-1500LVRT2UXL
Input: NEMA 5-15P (120V - 15A)
Output:
(6) NEMA 5-15R
Double-Conversion Online UPS - Sine wave Output
New batteries, refurbished UPS
1 Year Warranty Included

In stock

Manufacturer: Vertiv, Liebert
Model: Vertiv Liebert GXT5 UPS 1500VA 1350W RM 2U 120V - Online double conversion UPS

Condition: New batteries, refurbished UPS
Part Number: GXT5-1500LVRT2UXL
Maximum output:
1350W / 1500VA
Typical backup time
at half load: 18.8 minutes (675 Watts)
Typical backup time
at full load: 6.7 minutes (1350 Watts)
Warranty:
1 year full replacement warranty


Liebert GXT5 1500VA 1350W GXT5-1500LVRT2UXL User's Manual

 


GXT5-1500LVRT2UXL - Liebert UPS 1500VA / 1350W Specifications:


Physical:

Dimensions (inch/mm)

16.9 x 18.5 x 3.4 (430 x 470 x 85)

Weight (lbs/kg)

46.2 (21)


Input:

Range

Typical 120V
Range: 60-150V

Frequency

40-70Hz; Auto Sensing

Input Power Cord

10 ft. attached w/
NEMA 5-15P A plug


Output:

Output Receptacles

(6) NEMA 5-15R

Typical 120V
User selectable output

110/115/120VAC
(user-configurable); ±3%

Waveform

Sine wave

Utility (AC) Mode Overload

>200% for 250ms;
150- 200% for 2 seconds;
125- 150% for 50 seconds;
105-125% for 60 seconds


Battery:

Type

Valve-regulated, non-spillable, lead acid

Backup Time (100% Load)

6.7

Backup Time (50% Load)

18.8

+1 External Battery Cabinet
(100% Load)

32.4

+1 External Battery Cabinet
(50% Load)

79.7


Environmental Requirements:

Operating Temperature, °F (°C)

+32 to +104 (0 to 40)

Storage Temperature, °F (°C )

-4 to +140 (-20 to 60)
contain batteries will be
from -15 to 40°C

Relative Humidity

0% to 95%, non-condensing

Operating Elevation

10,000 ft. (3,000m)

Storage Elevation

50,000 ft. (15,000m)

Audible Noise

< 46dBA at 3 ft. (1m) front and side
< 45dBA at 3 ft. (1m) rear


Agency:

Surge Immunity

ANSI C62.41 Category B

Transportation

ISTA Procedure 1A

Safety

UL 1778 4th Edition and CSA
22.2 No 107.3

Emissions

FCC Part 15 (Class A) -
CISPR22 Class A (RFI)

Environmental

WEEE and ROHS2 REACH