Eaton Powerware 9130 UPS 3000VA 2700W 208V 20A TowerÂ
Model: PW9130G3000T-XL
Input: NEMA L6-20P (208V)
Output: (2) NEMA 6-20R, (1) NEMA L6-20R, (1) NEMA L6-30R
Topology: Online Double Conversion UPS – Pure Sine Wave Output
Condition: New batteries, Refurbished UPS
Warranty: 1 Year Warranty Included
In stock
Manufacturer: Eaton
Model: Eaton Powerware 9130 UPS 3000VA 2700W, 208V (Tower)
Condition: New batteries, refurbished UPS
Part Number: PW9130G3000T-XL
Maximum Output: 2700W / 3000VA
Typical Backup Time (Half Load): ~7–8 minutes (1350W aprox.)
Typical Backup Time (Full Load): ~3–4 minutes (2700W aprox.)
Warranty: 1 Year Full Replacement Warranty
Included: PW9130G3000T-XL UPS only (no accessories included)
Description:  Eaton Powerware 9130 PW9130G3000T-XL is a 3000VA / 2700W online double-conversion UPS designed for critical power protection in IT and network environments, delivering clean and stable pure sine wave output with high efficiency up to 94% in eco mode, featuring a 208V input via NEMA L6-20P connection and multiple output receptacles including NEMA 6-20R, L6-20R, and L6-30R, built in a rack/tower convertible form factor, equipped with internal hot-swappable sealed lead-acid batteries providing approximately 7–8 minutes runtime at half load and 3–4 minutes at full load, with optional external battery modules for extended runtime, includes advanced LCD interface for real-time monitoring, USB and serial communication ports with optional SNMP network management, supports remote monitoring, shutdown, and event logging, includes internal bypass, REPO support, and full protection features, refurbished with new batteries and backed by a 1-year full replacement warranty.
Â
Â
Eaton Powerware 9130 UPS 3000VA 2700W, 208V (Tower) - User Manual
Â
Eaton 9130 PW9130G3000T-XL - Specifications
General:
|
Topology |
Online (Double Conversion) |
|
Configuration |
Tower (Rack/Tower convertible) |
|
Color |
Black |
|
Rating (VA / W) |
3000VA / 2700W |
|
Efficiency |
Up to 94% (high-efficiency mode) |
|
Diagnostics |
Full system self-test |
|
Bypass |
Internal automatic bypass |
|
REPO |
Supported (Remote Emergency Power Off port) |
|
Dimensions (H × W × D) |
16.1 × 8.4 × 23.6 in |
|
Weight |
76.1 lb |
Â
Input:
|
Input Connection |
NEMA L6-20P |
|
Input Cord |
6 ft detachable |
|
Nominal Voltage |
208V |
|
Input Voltage Range |
176–276V (typical 208V operation) |
|
Frequency |
50/60 Hz |
|
Frequency Range |
45–65 Hz |
|
Nominal Current |
16A |
|
Generator Compatibility |
Yes |
Â
Output:
|
Receptacles |
(2) NEMA 6-20R, (1) L6-20R, (1) L6-30R |
|
Output Voltage |
208V (default) |
|
Voltage Regulation |
±2% |
|
Waveform |
Pure Sine Wave |
|
Power Factor |
0.9 |
|
Frequency Regulation |
±0.1 Hz (online mode) |
|
Load Crest Factor |
3:1 |
Â
Battery:
|
Battery Type |
Sealed Lead-Acid (VRLA) |
|
Battery Configuration |
Internal, hot-swappable |
|
Runtime (Half Load) |
~7–8 minutes |
|
Runtime (Full Load) |
~3–4 minutes |
|
Battery Replacement |
User replaceable |
|
Recharge Time |
4–6 hours to 90% |
|
External Battery Support |
Optional EBM supported |
Â
Communications & Management:
|
User Interface |
Graphical LCD display with multilingual support (status, load, battery, alarms) |
|
Front Panel Controls |
4-button navigation menu system |
|
LED Indicators |
Status LEDs for normal, battery, bypass, and alarm conditions |
|
Communication Ports |
(1) USB, (1) RS-232 serial, (1) relay alarm output |
|
Communication Slot |
1 × Eaton Mini-Slot (for optional communication cards) |
|
Remote Monitoring |
Supported via optional network card (SNMP/Web) |
|
Supported Protocols (via card) |
SNMP v1/v2c/v3, HTTP/HTTPS, SMTP (email alerts) |
|
Optional Network Management |
SNMP/Web card for browser-based monitoring and control |
|
Integration |
Compatible with network shutdown software (Eaton IPM / UPS Companion) |
|
Alarm Notifications |
Local alarms + remote alerts (via optional card) |
|
Event Logging |
Stored internally and accessible via software |
|
Remote Shutdown |
Supported via USB/RS232 software or network card |
|
Firmware Updates |
Supported via USB/software tools (network card required for remote updates) |
|
Dry Contact Relay |
Standard alarm relay output for external systems |
|
Security (via card) |
HTTPS, SNMPv3 authentication/encryption (optional) |
Â
Environmental & Standards:
|
Operating Temperature |
0°C to 40°C (32°F to 104°F) |
|
Storage Temperature |
-20°C to 50°C (-4°F to 122°F) |
|
Humidity |
0–95% non-condensing |
|
Noise Level |
~50 dBA |
|
Heat Dissipation |
~280 BTU/hr |
|
Certifications |
UL, cUL, CE, FCC Class A |
|
RoHS |
Yes |
Â