Tripp Lite SmartOnline 3000VA 2400W Tower
Model: SU3000XL
Input: NEMA L5-30P (120V - 30A)
Output: (4) NEMA 5-15R, (4) NEMA 5-15/20R, (1) NEMA L5-30R
Double Conversion Online UPS - Sinewave Output
New batteries, Refurbished UPS
1 Year Warranty Included
Back Order
Love Manufacturer: Tripp Lite
Model: Tripp Lite SmartOnline UPS 3000VA 2400W, Tower, 30A, 120V, New Batteries, Refurbished UPS
Condition: New batteries, refurbished UPS
Part Number: SU3000XL
Maximum output: 2400W / 3000VA
Typical backup time at half load: 14 minutes (1200 Watts)
Typical backup time at full load: 5 minutes (2400 Watts)
Warranty: 1 year full replacement warranty
Tripp Lite SmartOnline 3000VA 2400W Tower 120V SU3000XL User's Manual
SU3000XL - Tripp Lite SmartOnline 3000VA Specifications:
Input:
|
Rated input current (Maximum Load) |
24A (120V) |
||
|
Nominal Input Voltage(s) Supported |
110V AC; 120V AC |
||
|
UPS Input Connection Type |
|
||
|
Input Circuit Breakers |
40A |
||
|
UPS Input Cord Length (ft.) |
10 |
||
|
UPS Input Cord Length (m) |
3.1 |
||
|
Recommended Electrical Service |
30A 120V |
||
|
Input Phase |
Single-Phase |
Output:
|
Output Volt Amp Capacity (VA) |
3000 |
||||||
|
Output kVA Capacity (kVA) |
3 |
||||||
|
Output Watt Capacity (Watts) |
2400 |
||||||
|
Output kW Capacity (kW) |
2.4 |
||||||
|
Power Factor |
0.8 |
||||||
|
Crest Factor |
3:1 |
||||||
|
Nominal Voltage Details |
120V default |
||||||
|
Frequency Compatibility |
50 / 60 Hz |
||||||
|
Frequency Compatibility Details |
Output frequency matches input nominal on startup, defaults to 60 Hz on cold-start |
||||||
|
Output Voltage Regulation (Line Mode) |
+/- 2% |
||||||
|
Output Voltage Regulation (Economy Line Mode) |
+/- 10% |
||||||
|
Output Voltage Regulation (Battery Mode) |
+/- 2% |
||||||
|
Load Management Receptacles |
Two switchable four-outlet load banks, (bank 1 - four 5-15/20R, bank 2 - four 5-15R outlets) |
||||||
|
Output Circuit Breakers |
15A branch rated breaker (x2) protects 4 outlets each, L5-30R outlet is unbreakered |
||||||
|
Output AC Waveform (AC Mode) |
Pure Sine wave |
||||||
|
Output AC Waveform (Battery Mode) |
Pure Sine wave |
||||||
|
Output Capacity Details |
OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% load for 3 minutes; 150% |
||||||
|
Nominal Output Voltage(s) Supported |
110V; 120V |
||||||
|
Output Receptacles |
|
||||||
|
Individually Controllable Load Banks |
Yes |
Battery:
|
Full Load Runtime (min.) |
5 min. (2400w) |
|
Half Load Runtime (min.) |
14 min. (1200w) |
|
Expandable Battery Runtime |
Extended runtime supported via optional external battery packs |
|
External Battery Pack Compatibility |
BP72V15-2U (limit 1); BP72V28RT-3U (multi-pack compatible); BP72V18-2US (multi-pack compatible) |
|
DC System Voltage (VDC) |
72 |
|
Battery Recharge Rate (Included Batteries) |
Less than 6 hours from 10% to 80% (typical, full load discharge) |
|
Internal UPS Replacement Battery |
RBC96-3U |
|
Battery Access |
Front panel battery access door |
|
Battery Replacement Description |
Hot-swappable, user replaceable batteries |
|
Expandable Runtime |
Yes |
Voltage Regulation:
|
Voltage Regulation Description |
Online, double-conversion power conditioning |
|
Overvoltage Correction |
2% output voltage regulation during overvoltages to 150 |
|
Undervoltage Correction |
2% output voltage regulation during undervoltages to 80 |
|
Severe Undervoltage Correction |
2% output voltage regulation during undervoltages to 65 (under 70% load only) |
User Interface, Alerts & Controls:
|
Switches |
2 switches control off/on power status and alarm-cancel/self-test operation |
|
Audible Alarm |
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown |
|
LED Indicators |
14 LEDs indicate line power, online mode, economy/bypass mode, on-battery, overload, battery low, replace battery |
Surge / Noise Suppression:
|
UPS AC Suppression Joule Rating |
570 |
|
UPS AC Suppression Response Time |
Instantaneous |
|
UPS Dataline Suppression |
1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet |
|
EMI / RFI AC Noise Suppression |
Yes |
Physical:
|
Cooling Method |
Fan
|
|
Primary Form Factor |
Tower
|
|
Primary UPS Depth (mm) |
521
|
|
Primary UPS Height (mm) |
262 |
|
Primary UPS Width (mm) |
229 |
|
Shipping Dimensions (hwd / cm) |
37.34 x 58.67 x 32.00 |
|
Shipping Dimensions (hwd / in.) |
14.70 x 23.10 x 12.60 |
|
Shipping Weight (kg) |
33.75 |
|
Shipping Weight (lbs.) |
74.40 |
|
UPS Housing Material |
Steel |
|
UPS Power Module Dimensions (hwd, cm) |
26.16 x 22.86 x 52.07 |
|
UPS Power Module Dimensions (hwd, in.) |
10.3 x 9 x 20.5 |
|
UPS Power Module Weight (kg) |
31.43 |
|
UPS Power Module Weight (lbs.) |
69.3 |
Environmental:
|
Operating Temperature Range |
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
|
|
Storage Temperature Range |
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
|
Relative Humidity |
0 to 95%, non-condensing |
|
AC Mode BTU / Hr. (Full Load) |
1117 |
|
AC Economy Mode BTU / Hr. (Full Load) |
253 |
|
Battery Mode BTU / Hr. (Full Load) |
1225 |
|
AC Mode Efficiency Rating (100% Load) |
88% |
|
AC Economy Mode Efficiency Rating (100% Load) |
97% |
|
Audible Noise |
< 45 dB at front side 1m |
Communications:
|
Network Management Cards |
SNMPWEBCARD ; TLNETCARD ; WEBCARDLX ; MODBUSCARD ; RELAYIOCARD |
|
Network Monitoring Port Description |
Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure |
|
PowerAlert Software |
For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert |
|
Communications Cable |
USB and DB9 cabling included |
|
WatchDog Compatibility |
Supports Watchdog application, OS and hard-reboot restart options for remote applications |
|
Communications Interface |
Contact closure; DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface; USB (HID enabled) |