Tripp Lite SmartPro 3000VA 2880W RM 2U 120V 30A SMART3000RMXL2U - Refurbished

Tripp Lite SmartPro 3000VA 2880W RM 2U
Model: SMART3000RMXL2U
Input: NEMA L5-30P (120V - 30A)
Output: (8) NEMA 5-15/20R, (1) NEMA L5-30R
Line-Interactive UPS - Sinewave Output
New Batteries, Refurbished UPS
1 Year Warranty Included

Back Order

Manufacturer: Tripp Lite
Model:
Tripp Lite SmartPro UPS 3000VA 2880W,  RM, 2U, 120V
Condition:
New batteries, refurbished UPS
Part Number:
SMART3000RMXL2U

Maximum output: 2880W / 3000VA
Typical backup time
at half load:10 minutes (1440 Watts)
Typical backup time
at full load: 3 minutes (2880 Watts)
Warranty:
1 year full replacement warranty


Tripp Lite SmartPro 3000VA 2880W RM 120V SMART3000RMXL2U Manual


SMART3000RMXL2U - Tripp Lite SmartPro 3000VA Specifications:

Input:

Rated input current (Maximum Load)

24A

Nominal Input Voltage(s) Supported

120V AC

UPS Input Connection Type

NEMA L5-30P

UPS Input Cord Length (ft.)

10

UPS Input Cord Length (m)

3.1

Recommended Electrical Service

30A 120V

Input Phase

Single-Phase

Output:

Output Volt Amp Capacity (VA)

3000

Output Capacity (kVA)

3.00

Output Watt Capacity (Watts)

2880

Output kW Capacity (kW)

2.88

Power Factor

.96

Crest Factor

3:1

Nominal Voltage Details

120v nominal output in battery mode

Frequency Compatibility

60 Hz

Output Voltage Regulation (Line Mode)

+6%, -14%

Output Voltage Regulation (Battery Mode)

+/-5%

Load Management Receptacles

Two switchable single outlet 5-15/20R load banks

Output Circuit Breakers

Two 20A output breakers protect 4 5-15/20R outlets each

Output AC Waveform (AC Mode)

Pure Sine wave

Output AC Waveform (Battery Mode)

Pure Sine wave

Nominal Output Voltage(s) Supported

110V; 115V; 120V

Output Receptacles

(8) NEMA 5-15/20R

(1) NEMA L5-30R

Individually Controllable Load Banks

Yes


Battery:

Battery Type

Valve Regulated Lead Acid (VRLA)

Full Load Runtime (min.)

3 min. (2880w)

Half Load Runtime (min.)

10 min. (1440w)

Expandable Battery Runtime

Extended runtime supported via optional external battery packs

DC System Voltage (VDC)

48

Battery Recharge Rate (Included Batteries) 

Less than 5 hours from 10 to 90% (typical, full load discharge)

Battery Access

Front panel battery access door

Internal UPS Replacement Battery Cartridge

RBC58-2U

Battery Replacement Description

Hot-swappable, replaceable batteries

Expandable Runtime

Yes

Expandable Runtime Description

Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software, see manual for details

External Battery Pack Compatibility

BP48V24-2U  (limit 1);  BP48V60RT-3U  (multi-pack compatible);  BP48V27- 2US  (multi-pack compatible)


Voltage Regulation:

Voltage Regulation Description

Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 145

Overvoltage Correction

Input voltages between 127 and 145 are reduced by 12%

Undervoltage Correction

Input voltages between 108 and 96 are boosted by 12%

Severe Undervoltage Correction 

Input voltages between 83 and 95 are boosted by 24%


User Interface, Alerts & Controls:

Front Panel LCD Display

Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options)

Switches

3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions

Alarm Cancel Operation

Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available

Audible Alarm

Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions


Surge / Noise Suppression:

UPS AC Suppression Joule Rating

570

UPS AC Suppression Response Time

Instantaneous

EMI / RFI AC Noise Suppression

Yes


Physical:

Primary Form Factor

Rackmount

Cooling Method

Fan

Included Mounting Accessory Description

Included 4POSTRAILKIT mounting bracket enables installation in 4 post racks from 20.5 to 36 inches (521 to 914mm)

Installation Form Factors Supported with Included Accessories

4 post 19 inch rackmount

Installation Form Factors Supported with Optional Accessories

2 post rackmount ( 2POSTRMKITWM ); 4 post rackmount shortdepth ( 4POSTRAILKITWM ); Tower ( 2-9USTAND ); Wallmount ( 2POSTRMKITWM )

Minimum Required Rack Depth with External Battery Pack (cm)

67

Minimum Required Rack Depth with External Battery Pack (in.)

26.5

Minimum Required Rack Depth without External Battery Pack (cm)

62

Minimum Required Rack Depth without External Battery Pack (in.)

24.5

Optional Mounting Accessory Notes

Optional 2-9USTAND enables upright tower UPS placement; 2POSTRMKITWM enables wall-mount and 2-post rackmount installation; 4POSTRAILKITWM enables installation in 4-post short-depth racks from 14.5 to 23.5 inches (368 to 597mm); UPSHDEARKIT enables installation in 2 or 4-post racks using front vertical rails only, without rear support

Primary UPS Depth (mm)

483

Primary UPS Height (mm)

89

Primary UPS Width (mm)

445

Rack Height

2U

Shipping Dimensions (hwd / cm)

22.35 x 60.96 x 54.10

Shipping Dimensions (hwd / in.)

8.80 x 24.00 x 21.30

Shipping Weight (kg)

41.46

Shipping Weight (lbs.)

91.40

UPS Housing Material

Steel

UPS Power Module Dimensions (hwd, cm)

8.89 x 44.45 x 48.26

UPS Power Module Dimensions (hwd, in.)

3.50 x 17.50 x 19.00

UPS Power Module Weight (kg)

33.02

UPS Power Module Weight (lbs.)

72.8


Environmental:

Operating Temperature Range

+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius

Storage Temperature Range

+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius

Relative Humidity

0 to 95%, non-condensing

AC Mode BTU / Hr. (Full Load)

409

AC Economy Mode BTU / Hr. (Full Load)

294

Battery Mode BTU / Hr. (Full Load)

1736

AC Mode Efficiency Rating (100% Load)

96%

Audible Noise

45 dBA maximum, front side 1m


Communications:

Network Management Cards

SNMPWEBCARD ;  TLNETCARD ;  WEBCARDLX

Network Monitoring Port Description

Supports detailed monitoring of UPS and site power conditions

PowerAlert Software

For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at https://www.tripplite.com/poweralert

Communications Cable

USB, DB9 and EPO cabling included

WatchDog Compatibility

Supports Watchdog application, OS and hard-reboot restart options for remote applications

Network UPS Tools Compatibility

NUT compatible. See the full list of Tripp Lite NUT compatible UPS systems at http://www.networkupstools.org/stable-hcl.html?manufacturer=Tripp Lite

Network Management Card Description

Network management card optional

Communications Interface

DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface; USB (HID enabled)