Vertiv Liebert GXT5-2000LVRT2UXLN 2kVA - RDU101 UPS Online Double-Conversion - Refurbished

Vertiv Liebert GXT5 2000VA 1800W RM 2U 120V, RDU101 IntelliSlot Communications Card Pre-Installed
Model: GXT5-2000LVRT2UXLN
Input: NEMA L5-20P (120V - 20A)
Output: (1) NEMA L5-20R, (6) NEMA 5-20R
Double-Conversion Online UPS - Pure Sine Wave Output
New batteries, refurbished UPS
1 Year Warranty Included

In stock

Manufacturer: Vertiv / Liebert
Model: Vertiv Liebert GXT5 2000VA 1800W RM 2U 120V – Online Double-Conversion UPS (with RDU101 Network Card)
Condition: New batteries, refurbished UPS
Part Number: GXT5-2000LVRT2UXLN
Maximum Output: 1800W / 2000VA
Typical Backup Time at Half Load: 12.3 minutes (900 Watts)
Typical Backup Time at Full Load: 4 minutes (1800 Watts)
Warranty: 1-Year Full Replacement Warranty

Description: The Vertiv Liebert GXT5-2000LVRT2UXLN is a 2000VA / 1800W online double-conversion UPS designed for critical IT systems, delivering clean pure sine wave power with zero transfer time. It includes (1) NEMA L5-20R and (6) NEMA 5-20R output connections in a 2U rackmount form factor. Equipped with the pre-installed Vertiv Liebert IntelliSlot RDU101 Card network management card, it supports remote monitoring via SNMP and HTTPS, email notifications, event logging, and environmental monitoring capabilities. This refurbished unit includes new batteries and a 1-year full replacement warranty.

 

 


Vertiv Liebert GXT5 2000VA 1800W RM 2U 120V - User Manual





GXT5-2000LVRT2UXLN - Liebert UPS 2000VA / 1800W Specifications:

 

 

Input:

Input Voltage Range

Typical 120V Range: 60–150V

Input Voltage Range

40–70Hz; Auto Sensing

Input Power Cord

10 ft. attached with NEMA L5-20P plug

 

Output:

Output Receptacles (1) NEMA L5-20R
  (6) NEMA 5-20R
Typical 120V User Selectable Output 110/115/120VAC (user-configurable); ±3%
Waveform

Pure Sine Wave

Utility (AC) Mode Overload

>200% for 250ms

 

150–200% for 2 seconds

 

125–150% for 50 seconds

 

105–125% for 60 seconds
 
 
 

Battery: 

Battery Type Valve-regulated, non-spillable, lead acid
Backup Time (100% Load) 4 Minutes
Backup Time (50% Load) 12.3 Minutes
+1 External Battery Cabinet (100% Load)

22 Minutes

+1 External Battery Cabinet (50% Load)

53.6 Minutes

 

 

 

Environmental Requirements:

Operating Temperature, °F (°C) +32 to +104 (0 to 40)
Storage Temperature, °F (°C) -4 to +140 (-20 to 60)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation 10,000 ft. (3,000m)
Storage Elevation 50,000 ft. (15,000m)
Audible Noise <48dBA at 3 ft. (1m)

 

 

Communications & Management:

Control Interface LCD graphical display with keypad + secure web interface (HTTPS) via RDU101
Front Panel Color LCD for real-time UPS status, load %, battery level, alarms, and configuration
Remote Monitoring Full remote monitoring via embedded RDU101 network card
Network Interface 10/100 Mbps Ethernet (RJ-45) via RDU101
Communication Ports USB, RS-232, 1× RJ-45 Ethernet, 1× RJ-45 One-Wire
Communication Slot

 IntelliSlot (occupied by RDU101 card)

Supported Protocols

SNMP v1/v2c/v3, Modbus TCP/IP, HTTP/HTTPS, SMTP

Web Access

Secure HTTPS access (Chrome, Firefox, Safari, Edge compatible)

Remote Shutdown

Supported via network graceful shutdown software

Software Integration

Vertiv Power Insight, Trellis Enterprise, LIFE Services

Alarm Notifications

Email and SMS alerts

Alarm Types

Power failure, low battery, overload, temperature, system faults

Notifications

SNMP traps, email alerts, SMS (gateway dependent)

Environmental Monitoring

Supported via Liebert SN sensors

Sensor Interface

One-Wire port (RJ-45) for environmental sensors

Data Logging Event logs, alarm history, power conditions, environmental data
Firmware Upgrade Remote firmware/configuration updates
Security HTTPS encryption, SNMPv3, certificate support
Authentication

RADIUS, TACACS+, LDAP/Active Directory, Kerberos

User Access Control

Role-based multi-user access control

File Transfer

High-speed firmware/config uploads

Emergency Power Off (EPO)

Supported

 

 

 

 

 

Agency: 

Surge Immunity Surge Immunity
Transportation Transportation
Safety Safety
Emissions Emissions
Environmental Compliance Environmental Compliance