Vertiv Liebert 1500VA 1350W GXT5-1500LVRT2UXLN, RDU101 Double-Conversion Online - Refurbished

Vertiv Liebert GXT5 1500VA 1350W RM 2U 120V, RDU101 Intellislot Communications Card Pre-Installed
Model: GXT5-1500LVRT2UXLN
Input: NEMA 5-15P (120V - 15A)
Output:
(6) NEMA 5-15R
Double-Conversion Online UPS - Sine wave Output
New batteries, refurbished UPS
1 Year Warranty Included

In stock

Manufacturer: Vertiv, Liebert
Model: Vertiv Liebert GXT5 UPS 1500VA 1350W RM 2U 120V - Online double conversion UPS (with RDU101 Network Card)

Condition: New batteries, refurbished UPS
Part Number: GXT5-1500LVRT2UXLN
Maximum output:
1350W / 1500VA
Typical backup time
at half load: 18.8 minutes (675 Watts)
Typical backup time
at full load: 6.7 minutes (1350 Watts)
Warranty:
1 year full replacement warranty

Description:  The Vertiv Liebert GXT5-1500LVRT2UXLN is a 1500VA / 1350W online double-conversion UPS designed for critical IT systems, delivering clean sine wave power with zero transfer time. It includes (6) NEMA 5-15R outlets and a 2U rack/tower convertible design, with internal batteries providing up to 18.8 minutes of runtime at half load. Equipped with the RDU101 network card, it supports remote monitoring via SNMP and HTTPS, along with email/SMS alerts and environmental monitoring. This refurbished unit comes with new batteries and a 1-year full replacement warranty.

 


Liebert GXT5 1500VA 1350W GXT5-1500LVRT2UXLN - User's Manual

 

GXT5-1500LVRT2UXLN - Liebert UPS 1500VA / 1350W Specifications:

 

Input:

Range

Typical 120V
Range: 60-150V

Frequency

40-70Hz; Auto Sensing

Input Power Cord

10 ft. attached w/
NEMA 5-15P A plug


Output:

Output Receptacles

(6) NEMA 5-15R

Typical 120V
User selectable output

110/115/120VAC
(user-configurable); ±3%

Waveform

Sine wave

Utility (AC) Mode Overload

>200% for 250ms;
150- 200% for 2 seconds;
125- 150% for 50 seconds;
105-125% for 60 seconds


Battery:

Type

Valve-regulated, non-spillable, lead acid

Backup Time (100% Load)

6.7

Backup Time (50% Load)

18.8

+1 External Battery Cabinet
(100% Load)

32.4

+1 External Battery Cabinet
(50% Load)

79.7


Environmental Requirements:

Operating Temperature, °F (°C)

+32 to +104 (0 to 40)

Storage Temperature, °F (°C )

-4 to +140 (-20 to 60)
contain batteries will be
from -15 to 40°C

Relative Humidity

0% to 95%, non-condensing

Operating Elevation

10,000 ft. (3,000m)

Storage Elevation

50,000 ft. (15,000m)

Audible Noise

< 46dBA at 3 ft. (1m) front and side
< 45dBA at 3 ft. (1m) rear

Physical:

Dimensions (inch/mm)

16.9 x 18.5 x 3.4 (430 x 470 x 85)

Weight (lbs/kg)

46.2 (21)

 

Communications & Management (GXT5-1500LVRT2UXLN + RDU101):

Control Interface

LCD graphical display with keypad + secure web interface (HTTPS) via RDU101

Front Panel

Color LCD for real-time UPS status, load %, battery level, alarms, and configuration

Remote Monitoring

Full remote monitoring via embedded RDU101 network card

Network Interface

10/100 Mbps Ethernet (RJ-45) via RDU101

Communication Ports

USB, RS-232, 1× RJ-45 Ethernet, 1× RJ-45 One-Wire (environmental sensors)

Communication Slot

IntelliSlot (occupied by RDU101 card)

Supported Protocols

SNMP v1/v2c/v3, Modbus TCP/IP, HTTP/HTTPS, SMTP

Web Access

Secure HTTPS access (Chrome, Firefox, Safari, Edge compatible)

Remote Shutdown

Supported via network (graceful shutdown agents/software)

Software Integration

Vertiv Power Insight, Trellis Enterprise, LIFE Services

Alarm Notifications

Email and SMS alerts

Alarm Types

Power failure, low battery, overload, temperature, system faults

Notifications

SNMP traps, email alerts, SMS (gateway dependent)

Environmental Monitoring

Supported via Liebert SN sensors (temperature, humidity, leak, door status)

Sensor Interface

One-Wire port (RJ-45) for external environmental sensors

Data Logging

Event logs, alarm history, power conditions, environmental data

Firmware Upgrade

Remote firmware/config updates via HTTPS or HTTP API

Security

HTTPS encryption, SNMPv3 (MD5/SHA, DES/AES), certificate support

Authentication

RADIUS, TACACS+, LDAP/Active Directory, Kerberos

User Access Control

Role-based multi-user access control

File Transfer

High-speed firmware/config upload via web interface

Emergency Power Off (EPO)

Supported (hardware port on UPS)

 

Agency:

Surge Immunity

ANSI C62.41 Category B

Transportation

ISTA Procedure 1A

Safety

UL 1778 4th Edition and CSA
22.2 No 107.3

Emissions

FCC Part 15 (Class A) -
CISPR22 Class A (RFI)

Environmental

WEEE and ROHS2 REACH

Â