Vertiv Liebert PSI5 1100VA 990W Tower 120V PSI5-1100MT120 - Refurbished

Vertiv Liebert PSI5 1100VA 990W Tower 120V
Model: PSI5-1100MT120
Input: NEMA 5-15P (120V - 15A)
Output:
(3) NEMA 5-15R (Non-Controllable), (2) NEMA 5-15R (Controllable)
Line Interactive UPS - Sine wave Output
New batteries, refurbished UPS
1 Year Warranty Included

Back Order

Manufacturer: Vertiv
Model: Vertiv Liebert PSI5 UPS 1100VA 990W Tower 120V - Line Interactive UPS

Condition: New batteries, refurbished UPS
Part Number: PSI5-1100MT120
Maximum output:
 990W / 1100VA
Typical backup time
at half load: 14 minutes (495 Watts)
Typical backup time
at full load: 5 minutes (990 Watts)
Warranty:
1 year full replacement warranty


Vertiv Liebert PSI5 1100VA 990W PSI5-1100MT120 User's Manual

 


PSI5-1100MT120 - Vertiv UPS 1100VA / 990W Specifications:


Physical:

Dimensions (inch/mm)

5.7 x 14.8 x 8.7 (145 x 376 x 220)

Weight (Lb/kg)

29.1 (13.2)


Input/Output AC Parameters:

Nominal Voltage Setting

100 / 110 / 115 / 120 / 125 VAC

Voltage Input Range (with battery operation)

0-150VAC

Voltage Input Range (without battery operation)

75-146VAC

Input Voltage Measurement Tolerance

3%

High Line Buck to Battery

117 / 129/ 135 / 140 / 146 VAC


Standard Models:

Frequency Input Range

55-65 Hz (57-63 Hz Battery to Normal comeback)

Internal Rear-panel Input Breaker Rating

13A

Input Surge Protection

ANSI C62.41, Category A, Level 3 1372 J

Input Power Cord - offset 90-degree type (3m attached)

(1) NEMA 5-15P

Output Voltages (on battery)

100 / 110 / 115 / 120 / 125 VAC(±1.5 on battery before alarm) user selectable (120 VAC is factory default)

Output Frequency (on battery)

60 Hz ±1%

Output Receptacles - not controllable

(3) NEMA 5-15R

Output Receptacles - controllable

(2) NEMA 5-15R

Transfer Time

Adjustable with User Setting 09 ST1: 4-6ms typical, 10ms max (default) ST2: 4-6ms Typical, 11ms max ST3: 8-10ms typical, 13ms max

Battery Waveform

Pure Sinewave

Output Overload Operation

100%- alarm warning 110% - alarm warning and shutdown after 10 seconds 120%- alarm warning and immediate shutdown

Protection

Electronic (over current, short circuit w/ latching shutdown)

Buck- and Boost-mode Efficiency

93%

Type

Valve-regulated lead-acid (VRLA) in compliance with UL 1989

Recharge Time

6-8 hours to recover 90%

Quantity x Voltage x Ah

2 x 12V x 10Ah


Environmental:

Operating Temperature, °F (°C)

32-104 (0-40)

Storage Temperature °F (°C)

-5 - 122 (-15 - 50)

Relative Humidity

20% to 90% non-condensing

Operating Altitude

0 - 9,942 (0 -3,000) without derating Operating temperature reduced 9° F (5° C) for each additional 1,640 ft (500 m) of altitude.

Audible Noise

< 45 dB@line mode
< 55 dB@battery mode


Agency:

Safety

UL 1778, c-UL-us Listed

Emissions

FCC Part 15, Class B

Network Surge

UL 497 B

Transportation

ISTA Procedure 1A Certification