Description
Details
Manufacturer: Tripp Lite
Model: Tripp Lite SmartPro UPS 2200VA 1700W, Tower, 120V
Condition: New batteries, refurbished UPS
Part Number: SMART2200NET
Maximum output: 1700W / 2200VA
Typical backup time at half load: 27 minutes (850 Watts)
Typical backup time at full load: 11 minutes (1700 Watts)
Warranty: 1 year full replacement warranty
Tripp Lite SmartPro 2200VA 1700W Tower 120V SMART2200NET Manual
SMART2200NET - Tripp Lite SmartPro Specifications:
Input:
Rated input current (Maximum Load) |
15A |
||
Nominal Input Voltage(s) Supported |
120V AC |
||
UPS Input Connection Type |
|
||
Input Circuit Breakers |
20A |
||
UPS Input Cord Length (ft.) |
8 |
||
Recommended Electrical Service |
20A 120V |
||
Input Phase |
Single-Phase |
||
Input Cord Length (ft.) |
8 |
Output:
Output Volt Amp Capacity (VA) |
2200 |
||
Output kVA Capacity (kVA) |
2.2 |
||
Output Watt Capacity (Watts) |
1700 |
||
Output kW Capacity (kW) |
1.7 |
||
Output Capacity Details |
Output is reduced to 1200W maximum with 1-2 external battery packs and 800W maximum with 3 or more external |
||
Power Factor |
0.8 |
||
Nominal Voltage Details |
120v nominal output in battery mode |
||
Frequency Compatibility |
60 Hz |
||
Output Voltage Regulation (Line Mode) |
-13% / +5% |
||
Output Voltage Regulation (Battery Mode) |
+/- 5% |
||
Load Management Receptacles |
Two switchable single outlet 5-15R load banks |
||
Output AC Waveform (AC Mode) |
Sine wave |
||
Output AC Waveform (Battery Mode) |
PWM sine wave |
||
Nominal Output Voltage(s) Supported |
110V; 115V; 120V |
||
Output Receptacles |
|
||
Individually Controllable Load Banks |
Yes |
Battery:
Full Load Runtime (min.) |
11 min. (1700w) |
Half Load Runtime (min.) |
27 min. (850w) |
Expandable Battery Runtime |
Extended runtime supported via optional external battery packs |
Expandable Runtime |
Yes |
External Battery Pack Compatibility |
BP24V28-2U (limit 1); BP24V70-3U (multi-pack compatible) |
DC System Voltage (VDC) |
24 |
Battery Recharge Rate (Included Batteries) |
Less than 9 hours from 10% to 90% (typical, full load discharge) |
Voltage Regulation:
Voltage Regulation Description |
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 87 to 140 |
Overvoltage Correction |
Input voltages between 127 and 140 are reduced by 12% |
Undervoltage Correction |
Input voltages between 95 and 105 are boosted by 10% |
Severe Undervoltage Correction |
Input voltages between 87 and 94 are boosted by 22% |
User Interface, Alerts & Controls:
Switches |
2 Switches control off/on power status and alarm-cancel/self-test operation; set of 4 rear-panel switches control system enable and contact closure port inverter shutoff commands |
Alarm Cancel Operation |
Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate lowbattery status |
Audible Alarm |
Audible alarm indicates power-failure and low-battery conditions |
LED Indicators |
5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status |
Surge / Noise Suppression:
UPS AC Suppression Joule Rating |
720 |
UPS AC Suppression Response Time |
Instantaneous |
EMI / RFI AC Noise Suppression |
Yes |
Physical:
Primary Form Factor |
Tower
|
Primary UPS Depth (mm) |
318 |
Primary UPS Height (mm) |
432 |
Primary UPS Width (mm) |
229 |
UPS Housing Material |
Polycarbonate |
UPS Power Module Dimensions (hwd, in.) |
17 x 9 x 12.5 |
UPS Power Module Weight (kg) |
36.29 |
UPS Power Module Weight (lbs.) |
80 |
Environmental:
Operating Temperature Range |
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
|
Storage Temperature Range |
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
Relative Humidity |
0 to 95%, non-condensing |
AC Mode BTU / Hr. (Full Load) |
59 |
Battery Mode BTU / Hr. (Full Load) |
867 |
AC Mode Efficiency Rating (100% Load) |
99% |
Communications:
Network Monitoring Port Description |
Supports detailed monitoring of UPS and site power conditions; contact closure communications via two additional DB9 ports (3 total) |
PowerAlert Software |
For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at https://www.tripplite.com/poweralert |
Communications Cable |
3 DB9 cables included |
Network Management Card Description |
Network management not supported |
Communications Interface |
Contact closure; DB9 Serial |
Additional Info
Additional Info
Manufacturer | Tripp Lite |
---|---|
Form Factor | Tower |
Waveform in Battery Mode | Pure Sinewave |
Input Voltage | 120V AC |
Output (VA) | 2200VA |
Output Voltage | 120V AC |
PDU Total Outlets | No |